Type |
N/A Digital Indicator |
Series |
N/A 1800 |
Process Display |
N/A 4 digit, 0.4" liquid crystal display (-1999 to 9999) |
Operating Temperature [Min] |
N/A -20 ºC-4 ºF |
Operating Temperature [Max] |
N/A 50 ºC122 ºF |
Input Signals |
N/A 4 to 20 mA |
Accuracy1 | N/A <0.2 % |
Digit Accuracy (±) |
N/A 1 % |
Storage Temperature |
N/A -4 to 153 ºF-20 to 70 ºC |
Effect |
N/A ≤ 0.1% of Full Scale/18 ºF (10 ºC) % |
Full Scale Temperature |
N/A 18 ºF10 ºC |
Environmental Rating |
N/A IP65 per EN60529 |
Input Signals Current |
N/A 4 to 20 mA |
Optional Direct Current (DC) Voltage |
N/A 0 to 10 V |
Key Pad |
N/A 3 programmable function keys for relay option only, located behind the face plate |
Power Requirement |
N/A Loop powered by sensors excitation |
Power Consumption [Max] |
N/A 40 mA |
Drop Direct Current (DC) Voltage |
N/A ≤ 2 V |
Electrical Connection |
N/A DIN 175301-803 Form A |
Memory |
N/A Electrically Erasable Programmable Read-Only Memory (EEPROM) |
Non-Condensing Humidity |
N/A <90 % |
Update Rate |
N/A 200 ms |
Selectable Filtering |
N/A 0.2 to 1.5 s |
Relay Option |
N/A 1 Transistor, N-Switching |
Linearization |
N/A 2 Point |
Electromagnetic Rating |
N/A European Conformity (CE) Compliant to Electromagnetic Compatibility (EMC) Norm European Standards (EN) 61326-1, Radio Frequency Interference (RFI), Electromagnetic Interference (EMI) and Electrostatic Discharge (ESD) Protection |
Weight |
N/A 3 oz |
Warranty |
N/A 1 y |
Options |
N/A With Relay |
Limitations Which Apply Are |
N/A
These units must be operated within the catalogued environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation. In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice. |
Application |
N/A
|
Additional Information |
N/A
|