Print Back
  • High accuracy 4 mA to 20 mA loop-powered indicators for NOSHOK 11 Series Sanitary, 300, 615/616 Series pressure transmitters and 800 Series temperature transmitters
  • Can be fitted to NOSHOK pressure transmitters utilizing a 4 mA to 20 mA output signal and the DIN 175301-803 Form A connector
  • Easily inserted between the transmitter body and the connector
  • Programmable to display a range of -1999 to 9999; may be tilted for better viewing
Unit of Measure

Specifications

Type

N/A Digital Indicator

Series

N/A 1800

Process Display

N/A 4 digit, 0.4" liquid crystal display (-1999 to 9999)

Operating Temperature [Min]

N/A -20 ºC-4 ºF

Operating Temperature [Max]

N/A 50 ºC122 ºF

Input Signals

N/A 4 to 20 mA
Accuracy1 N/A <0.2 %

Digit Accuracy (±)

N/A 1 %

Storage Temperature

N/A -4 to 153 ºF-20 to 70 ºC

Effect

N/A ≤ 0.1% of Full Scale/18 ºF (10 ºC) %

Full Scale Temperature

N/A 18 ºF10 ºC

Environmental Rating

N/A IP65 per EN60529

Input Signals Current

N/A 4 to 20 mA

Optional Direct Current (DC) Voltage

N/A 0 to 10 V

Key Pad

N/A 3 programmable function keys for relay option only, located behind the face plate

Power Requirement

N/A Loop powered by sensors excitation

Power Consumption [Max]

N/A 40 mA

Drop Direct Current (DC) Voltage

N/A ≤ 2 V

Electrical Connection

N/A DIN 175301-803 Form A

Memory

N/A Electrically Erasable Programmable Read-Only Memory (EEPROM)

Non-Condensing Humidity

N/A <90 %

Update Rate

N/A 200 ms

Selectable Filtering

N/A 0.2 to 1.5 s

Relay Option

N/A 1 Transistor, N-Switching

Linearization

N/A 2 Point

Electromagnetic Rating

N/A European Conformity (CE) Compliant to Electromagnetic Compatibility (EMC) Norm European Standards (EN) 61326-1, Radio Frequency Interference (RFI), Electromagnetic Interference (EMI) and Electrostatic Discharge (ESD) Protection

Weight

N/A 3 oz

Warranty

N/A 1 y

Options

N/A With Relay

Limitations Which Apply Are

Limitations Which Apply Are

N/A These units must be operated within the catalogued environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation.

In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice.

Application

Application

N/A
  • Hydraulic and pneumatic systems
  • Pumps and compressors
  • Test equipment and systems
  • Industrial machinery and machine tools
  • Heating, Ventilation, and Air Conditioning (HVAC)
  • Power generation
  • Water and wastewater
  • Stamping and forming presses

Additional Information

Additional Information

N/A
  • User selectable digital filtering improves readability in rapidly varying pressure applications
  • All parameters are stored in non-volatile memory so that reprogramming is not necessary in the event of a power failure
  • Currently used with 300 Series Pressure Transmitter and 800 Series Temperature Transmitter

Options and Accessories

Installed Options and Accessories

N/A Optional Relay - 1 x NPN Switch (1)

Note

Note

N/A Indicate display range or order eg. 0-1,000 for 4 mA to 20 mA.
  • 1 Max. error on complete span. Error at calibration point ≤0.1 ºC