Items |
![]() 810--22/125-1-1-2-25-010-6 810 Series Compact Temperature Transmitter, -22/125 ºF Temperature Range, 4-20 mA Output, 1/4 NPT Process Connection, M12 x 1 (4-Pin), 1.0 in Stem, 6 mm Diameter |
![]() 810--22/250-1-1-2-25-010-6 810 Series Compact Temperature Transmitter, -22/250 ºF Temperature Range, 4-20 mA Output, 1/4 NPT Process Connection, M12 x 1 (4-Pin), 1.0 in Stem, 6 mm Diameter |
![]() 810-0/100-1-1-2-25-010-6 810 Series Compact Temperature Transmitter, 0/100 ºF Temperature Range, 4-20 mA Output, 1/4 NPT Process Connection, M12 x 1 (4-Pin), 1.0 in Stem, 6 mm Diameter |
![]() 810-0/200-1-1-2-25-010-6 810 Series Compact Temperature Transmitter, 0/200 ºF Temperature Range, 4-20 mA Output, 1/4 NPT Process Connection, M12 x 1 (4-Pin), 1.0 in Stem, 6 mm Diameter |
![]() 810-0/300-1-1-2-25-010-6 810 Series Compact Temperature Transmitter, 0/300 ºF Temperature Range, 4-20 mA Output, 1/4 NPT Process Connection, M12 x 1 (4-Pin), 1.0 in Stem, 6 mm Diameter |
|||||
Description |
N/A
|
|||||||||
Type | N/A Transmitter | |||||||||
Connection Type | N/A Male National Pipe Thread (MNPT) | |||||||||
Seal Material | N/A 316 Stainless Steel | |||||||||
Low Calibrated Temperature Range | N/A -22 ºF | N/A -22 ºF | N/A 0 ºF | N/A 0 ºF | N/A 0 ºF | |||||
High Calibrated Temperature Range | N/A 125 ºF | N/A 250 ºF | N/A 100 ºF | N/A 200 ºF | N/A 300 ºF | |||||
Housing Material | N/A 316 Stainless Steel | |||||||||
Connection Size | N/A 1/4 in | |||||||||
Output Signal | N/A 4 to 20 mA, 2-Wire | |||||||||
Electrical Connection | N/A M12 x 1 (4-Pin) | |||||||||
Power Supply | N/A 10 to 30 Vdc | |||||||||
Accuracy1 |
N/A
±0.80 ºF (± 0.45 ºC) Maximum uncertainty calculated @ maximum span, maximum measurement temperature, and ambient temperature. Maximum uncertainty includes Usensing element, Usensor measurement, Uoutput linearization. |
|||||||||
Storage Temperature [Max] | N/A 85 ºC185 ºF | |||||||||
Storage Temperature [Min] | N/A -40 ºC-40 ºF | |||||||||
Series | N/A 810 | |||||||||
Standard Temperature Ranges | N/A -22 to 302 ºF | |||||||||
Sensor Protection | N/A Burnout Protected from 3.3 to 23 mA | |||||||||
Measuring Element | N/A PT1000 Class A | |||||||||
Load Limitations | N/A ≤(Supply Voltage - 10 Volts)/0.023 A | |||||||||
Pressure Rating | N/A 3,915 psi | |||||||||
Ambient Temperature Range | N/A -40 to 185 ºF-40 to 85 ºC | |||||||||
Environmental Protection | N/A Ingress Protection (IP67) | |||||||||
Electrical Protection | N/A Reverse polarity, over-voltage and short circuit protection | |||||||||
Warranty | N/A 3 y | |||||||||
Measuring Element Accuracy | N/A PT1000 Class A | |||||||||
Temperature Sensor Accuracy |
N/A
For ºF: ±[1.8*(0.15 + 0.002 (t - 32) / 1.8)] For ºC: ±(0.15 K + 0.002 I t I) per EN 60751 |
|||||||||
Sensor Diameter | N/A 6 mm | |||||||||
Sensor Length | N/A 1 in | |||||||||
Industry Standards/Certifications |
N/A
European Conformity (CE) Compliant to Electromagnetic Compatibility (EMC) per EN 61326 Radio Frequency Interference (RFI), Electromagnetic Interference (EMI) and Electrostatic Discharge (ESD) Protection |
|||||||||
Prop 65 Warnings |
N/A
![]() |
|||||||||
Limitations Which Apply Are |
N/A
These units must be operated within the catalogued environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation. In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice. |
|||||||||
Thermowells | N/A Thermowells allow a temperature instrument to be removed and replaced without shutting down and draining the process, and reduce the possibility of damage to the temperature instrument. | |||||||||
Application |
N/A
|
|||||||||
Note | N/A Thermowells are recommended for pressure, corrosive fluids and high velocity applications. | N/A | N/A | N/A | N/A | |||||
|