Skip To Content

Catalog

Intelligent Pressure Transmitter, Min. span 1.45 psi, max. span 5.8 psi (lowest vacuum pressure -5.8 psig), ±0.2% of adjusted span with 4:1 turn down, 4 mA to 20 mA, 2-wire, 1-1/2" National Pipe Thread (NPT) male flush, M12 x 1 4 pin, transparent cover
Unit of Measure

Specifications

Product Series

PTI20 Intelligent Pressure Transmitter

Pressure Range

Min. span 1.45 psi, max. span 5.8 psi (lowest vacuum pressure -5.8 psig)
Accuracy1 ±0.2% of adjusted span with 4:1 turn down

Output Signal

4 mA to 20 mA, 2-wire

Process Connection

1-1/2" National Pipe Thread (NPT) male flush

Electrical Connection

M12 x 1 4 pin

Environmental Rating

IP66

Power Requirement

12 Vdc to 36 Vdc

Materials Of Construction (Wetted Parts)

316 Stainless Steel with 304 Stainless Steel housing

Media Temperature Range

-4 to 176 ºF-20 to 80 ºC

Applications

  • Food & beverage
  • Pulp & paper
  • Water & wastewater
  • Power generation
  • General Industrial

Related Items

Related Items

, 1/2" National Pipe Thread (NPT), Male x Female, 316 Stainless Steel, Hard Seat, 0.187" Orifice Block and Bleed 2-Valve ($320.88)
, 1/2" National Pipe Thread (NPT), Male x Female, 316 Stainless Steel, Soft Seat, 0.187" Orifice Needle Valve ($193.25)

Additional Technical Information

Stability

<0.1%/year

Adjustment

By 3 push buttons on display or optional HART® protocol

Response Time

<100 ms

Service Life

>10 y

Ambient Temperature Range

-4 to 158 ºF-20 to 70 ºC

Flange Temperature Range

-4 to 212 ºF-20 to 100 ºC

Connection Material

316 Stainless Steel

Measuring Element

316 Stainless Steel (Hastelloy C or Tantalum optional)

Approximate Weight

3.3 lb

Options and Accessories

Options

TC Transparent Cover (for display)

Digital Indicators

NOSHOK Digital Indicators provide local indication for pressure, level and temperature transmitters.

Limitations Which Apply Are

Limitations Which Apply Are

These units must be operated within the catalogued environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation.

In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice.

Prop 65 Warnings

Prop 65 Warnings

WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • 1 Max. error on complete span. Error at calibration point ≤0.1 ºC