Skip To Content

Catalog

Using the 5-valve manifold
In normal operation the “isolate” valves are open while the "equalize" and "vent" valves are closed. This provides a differential pressure reading to the pressure gauge or transmitter.
To zero the instrument, first close both “vent” valves and the downstream "isolate" valve. Then open the "equalize" valve and adjust the zero setting on the instrument.
To remove the instrument, first close both "isolate" valves, then open the "equalize" valves to relieve pressure between the manifold and the instrumet.

Note: The body & trim parts on all 316/316L Valves & Manifolds comply to NACE MR-01-75 & NORSOK M-650 as standard.
Unit of Measure

Specifications

Tip

N/A Hard

Packing

N/A GRAFOIL

Inlet Connection

N/A Integral Metric

Inlet Size

N/A 10 mm

Alloy

N/A 316/316L

Weight

N/A 5.95 lb2.7 kg

Maximum pressure at 212 ºF (100 ºC)

N/A 6000 psi413 bar

Maximum pressure at 842 ºF (450 ºC)

N/A 3300 psi230 bar

Calibration Option

N/A An option provided by 5-valve manifolds which is not available on 3-valve types is connecting the "vent" port to known pressure sources to check the calibration of the instrument.

Pressure Equipment Directive

N/A Due to internal bore size and internal volumes up to and including 1"/25mm, products offered in this catalogue comply with S.E.P (Sound Engineering Practice) article 3, paragraph 3 of the Pressure Equipment Directive P.E.D. 97/23/EC and therefore CE marking is not applicable.

Back to Top