Skip To Content

Catalog

  • Proven PT1000 platinum resistance sensor provides reliability, stability and unbeatable performance
  • Standard temperature ranges from -22 ºF to 302 ºF (-30 ºC to 150 ºC)
  • 4 mA to 20 mA transmitter included
Unit of Measure

Specifications

Type

Transmitter

Connection Type

Male National Pipe Thread (MNPT)

Seal Material

316 Stainless Steel

Low Calibrated Temperature Range

0 ºF

High Calibrated Temperature Range

200 ºF

Housing Material

316 Stainless Steel

Connection Size

1/4 in

Output Signal

4 to 20 mA, 2-Wire

Electrical Connection

M12 x 1 (4-Pin)

Power Supply

10 to 30 Vdc
Accuracy1 ±0.80 ºF (± 0.45 ºC)
Maximum uncertainty calculated @ maximum span, maximum measurement temperature, and ambient temperature. Maximum uncertainty includes Usensing element, Usensor measurement, Uoutput linearization.

Storage Temperature [Max]

85 ºC185 ºF

Storage Temperature [Min]

-40 ºC-40 ºF

Series

810

Standard Temperature Ranges

-22 to 302 ºF

Sensor Protection

Burnout Protected from 3.3 to 23 mA

Measuring Element

PT1000 Class A

Load Limitations

≤(Supply Voltage - 10 Volts)/0.023 A

Pressure Rating

3,915 psi

Ambient Temperature Range

-40 to 185 ºF-40 to 85 ºC

Environmental Protection

Ingress Protection (IP67)

Electrical Protection

Reverse polarity, over-voltage and short circuit protection

Warranty

3 y

Measuring Element Accuracy

PT1000 Class A

Temperature Sensor Accuracy

For ºF: ±[1.8*(0.15 + 0.002 (t - 32) / 1.8)]
For ºC: ±(0.15 K + 0.002 I t I) per EN 60751

Sensor Diameter

6 mm

Sensor Length

1 in

Industry Standards/Certifications

European Conformity (CE) Compliant to Electromagnetic Compatibility (EMC) per EN 61326
Radio Frequency Interference (RFI), Electromagnetic Interference (EMI) and Electrostatic Discharge (ESD) Protection

Prop 65 Warnings

Prop 65 Warnings

WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Limitations Which Apply Are

Limitations Which Apply Are

These units must be operated within the catalogued environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation.

In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice.

Thermowells

Thermowells

Thermowells allow a temperature instrument to be removed and replaced without shutting down and draining the process, and reduce the possibility of damage to the temperature instrument.

Application

Application

  • Mobile hydraulics
  • Automotive
  • Heat exchangers
  • HVAC
  • Transportation
  • Refrigeration controls
  • 1 Max. error on complete span. Error at calibration point ≤0.1 ºC